Technical
Specification for Stationary VLA - Cells
|
| 1.
Application
BAE OPzS - Batteries belong
to the most
enduring lead acid batteries.They
are suitable
for stand - by operations
as well as for capacitive loads. They perfectly meet requirements for bridging
times between 1h and more than 10h.
Fields:
Telecommunications
Emergency lighting
Microwave radio systems
Power generation plants
Photovoltaics
|
|
|
| |
| 2. Types, capacities
(acc. DIN 40736 part1)*, dimensions, mass |
|
Type
|
C10
|
C5
|
C3
|
C1
|
Ri
1)
|
Ik
2)
|
length
|
width
|
height
max
|
mass
3)
|
mass
4)
|
| . |
Ah
|
Ah
|
Ah
|
Ah
|
mW
|
kA
|
mm
|
mm
|
mm
|
kg
|
kg
|
|
Ue V/cell
|
1,80
|
1,77
|
1,75
|
1,67
|
. |
. |
. |
. |
. |
. |
. |
|
4 OPzS 200
|
210
|
175
|
156
|
114
|
0,95
|
2,16
|
105
|
208
|
420
|
12,2
|
17,2
|
|
5 OPzS 250
|
270
|
220
|
195
|
143
|
0,76
|
2,70
|
126
|
208
|
420
|
14,6
|
20,8
|
|
6 OPzS 300
|
320
|
262
|
234
|
170
|
0,63
|
3,24
|
147
|
208
|
420
|
17,2
|
24,3
|
|
5 OPzS 350
|
400
|
336
|
282
|
205
|
0,70
|
2,90
|
126
|
208
|
535
|
18,9
|
26,9
|
|
6 OPzS 420
|
490
|
400
|
339
|
245
|
0,58
|
3,48
|
147
|
208
|
535
|
22,2
|
31,5
|
|
7 OPzS 490
|
570
|
470
|
396
|
285
|
0,50
|
4,06
|
168
|
208
|
535
|
25,2
|
36,1
|
|
6 OPzS 600
|
670
|
560
|
474
|
330
|
0,47
|
4,32
|
147
|
208
|
710
|
31,9
|
44,8
|
|
8 OPzS 800
|
890
|
740
|
633
|
440
|
0,35
|
5,76
|
215
|
193
|
710
|
44,2
|
61,3
|
|
10 OPzS 1000
|
1120
|
930
|
789
|
550
|
0,28
|
7,20
|
215
|
235
|
710
|
52,3
|
74,5
|
|
12 OPzS 1200
|
1340
|
1100
|
948
|
660
|
0,23
|
8,64
|
215
|
277
|
710
|
62,1
|
88
|
|
12 OPzS 1500
|
1690
|
1400
|
1200
|
820
|
0,23
|
9,18
|
215
|
277
|
855
|
80,4
|
114,3
|
|
16 OPzS 2000
|
2250
|
1850
|
1600
|
1100
|
0,17
|
12,24
|
215
|
400
|
815
|
102,5
|
151,5
|
|
20 OPzS 2500
|
2810
|
2300
|
2000
|
1375
|
0,14
|
15,30
|
215
|
490
|
815
|
129,8
|
193
|
|
24 OPzS 3000
|
3380
|
2800
|
2400
|
1640
|
0,11
|
18,36
|
215
|
580
|
815
|
159,4
|
234,5
|
|
| 1, 2)
internal resistance and short - circuit
- current from IEC 896-1 |
3) dry-charged |
4) filled and charged |
|
|
|
|
4 OPzS 200
to 6 OPzS 600
|
8 OPzS 800
to 12 OPzS 1500
|
|
|
|
16
OPzS 2000
|
20 OPzS 2500
to 24 OPzS 3000
|
|
|
| 3.Design |
| positive electrode |
tubular
- plate with a woven polyester gauntlet and solid grids in a corrosion-
resistant PbSb1.6SnSe - alloy |
| negative electrode |
grid -
plate in low antimony alloy with long - life expander material
|
| separation |
microporous
separator |
| elektrolyte |
sulphuric
acid with a density of 1,24 kg/l, |
| container |
high impact,
transparent SAN (Styrol-Acryl-Nitril) |
| lid |
SAN in
dark grey colour |
| plugs |
labyrinth
plugs for arresting aerosol, optional ceramic plugs or ceramic funnel plugs
according DIN 40 740 |
| pole - bushing |
100% gas-
and electrolyte-tight, sliding-pole |
| kind of pole |
M10 brass
insertion |
| connectors |
flexible
insulated copper cables, with cross-section of
35, 50, 70, 95 or 120 mm² |
| kind of protection |
IP 25
regarding DIN 40050, touch protected according VBG 4. |
|
| |
| 4. Charging |
| IU
- characteristic |
Imax
without limitation
U = 2,23 V/cell +- 1%, between
10°C and 55°C
D U/D T = -0,004 V/K below
10°C in the monthly average |
| boost charge |
U = 2,35
to 2,40V/cell, time limited |
| charging time up to 88% |
6h with
1,5*I10 initial current, 2.23 V/cell, 50% C10 discharged |
|
| |
| 5. Discharge characteristics |
| reference temperature |
20°C |
| initial capacity |
100% |
| depth of discharge (DOD) |
normally
up to 80% |
| deep discharges |
more than
80% DOD or discharges beyond final discharge
voltages (dependent on discharge
current) have to be avoided |
|
| |
| 6. Maintenance |
| every 6 months |
check
battery voltage, pilot block voltage, temperature |
| every 12 months |
record
battery and block voltages and temperatures |
|
| |
| 7. Operational data |
| operational
life |
>
16 years at 20°C
|
| water - refilling - interval |
more than
3 years at 20°C |
| IEC 896-1 cykles |
1500 |
| self-discharge |
app. 3%
per month at 20°C |
| operational temperature |
-20°C
to 55°C
recommended 10°C to
30°C |
| ventilation requirement |
50% f1=0,5
due to low antimony alloy, VDE 0510 part 2 |
| standard |
DIN 40
736 part 1 |
| tests according |
IEC 896-1, |
| safety standard |
VDE 0510,
part 2 |
| transport |
no dangerous
goods during road transport |
|
| |
| Tell us your application.
We support you in the selection of your battery. |
|