Technical Specification for Stationary VLA - Cells
1. Application

BAE OGi - cells are suitable for safety batteries where operational safety and long operational life has top priority and high discharge currents during short discharge times and capacitive loads over longer discharge times are required.

They are used as standby source in power supply stations, transforming stations, UPS - stations, emergency light equipment acc. VDE 0108 and VDE 0107 and photovoltaic applications.

The round-grid plate used by BAE grant due to the high lead weight and the circular bars a long operational life and a very good high - current - performance. The straight - walled containers and the supported plates offer a high power - density related to the small foot-print. The transparent containers allows an all-round - control and they make service and maintenance easier. 

 

2. Types, capacities, dimensions, mass
Type
C10
C5
C3
C1
C1/2
C1/6
R1)
IKs  2)
length
width
height max
Mass 
3)
Mass 4)
.
Ah
Ah
Ah
Ah
Ah
Ah
mW
kA
mm
mm
mm
kg
kg
Ue V / cell
1,80
1,80
1,79
1,75
1,65
1,55
 . . . . . . .
5 OGi 400
443
361
309
207
160
109
0,450
4,5
145
206
700
26,5
40
6 OGi 480
500
413
358
243
191
128
0,375
5,4
145
206
700
30,5
43
7 OGi 560
556
465
403
280
223
147
0,321
6,3
145
206
700
34,5
47
8 OGi 640
613
515
451
316
254
166
0,281
7,2
145
206
700
38,0
51
9 OGi 720
670
570
500
352
286
185
0,250
8,1
145
206
700
42,0
54
10 OGi 800
780
655
570
397
320
218
0,225
9,0
210
191
700
49,5
62
11 OGi 880
836
705
618
433
351
237
0,205
9,9
210
191
700
53,5
68
12 OGi 960
893
760
667
469
382
256
0,188
10,8
210
191
700
57,5
73,5
13 OGi 1040
1000
845
736
514
414
276
0,173
11,7
210
233
700
62,0
78
14 OGi 120 
1060
895
785
550
446
296
0,161
12,6
210
233
700
66,0
84
15 OGi 1200
1120
950
830
587
477
315
0,150
13,5
210
233
700
70,0
88
16 OGi 1280
1230
1035
903
632
508
333
0,141
14,4
210
275
700
74,5
94
17 OGi 1360
1280
1085
951
668
540
352
0,132
15,3
210
275
700
78,5
98
18 OGi 1440
1340
1140
997
704
571
371
0,125
16,2
210
275
700
82,0
102
19 OGi 1520
1500
1250
1088
754
603
403
0,118
17,1
218
368
675
87,5
125
20 OGi 1600
1550
1305
1136
790
634
422
0,113
18,0
218
368
675
91,5
126
21 OGi 1680
1610
1355
1182
826
665
442
0,107
18,9
218
368
675
95,0
128
22 OGi 1760
1670
1405
1230
863
697
461
0,102
19,8
218
368
675
99,0
130
23 OGi 1840
1720
1460
1279
899
728
480
0,098
20,7
218
368
675
103,0
133
24 OGi 1920
1780
1510
1324
935
759
497
0,094
21,6
218
368
675
107,0
135
25 OGi 2000
1940
1630
1421
988
790
516
0,090
22,5
218
448
675
112,0
148
26 OGi 2080
2000
1680
1467
1024
821
535
0,087
23,4
218
448
675
115,5
150
27 OGi 2160
2050
1735
1515
1060
853
554
0,083
24,3
218
448
675
119,5
153
28 OGi 2240
2110
1785
1560
1096
884
573
0,080
25,2
218
448
675
123,5
156,5
29 OGi 2320
2170
1835
1609
1132
915
591
0,078
26,1
218
448
675
127,5
158
30 OGi 2400
2220
1890
1657
1168
946
610
0,075
27,0
218
448
675
131,5
160
1), 2)  inner resistance and short-circuit current according to IEC 896-1  3) drycharged  4) filled and charged
5 OGi 400 to 9 OGi 720
10 OGi 800 to 18 OGi 1440
19 OGi 1520 to 30 OGi 2400

 

3. Design
positive electrode  round-grid plate with low antimony alloy (1,6%), circular bars
high lead weight
negative electrode  flat plate with long life expander and low antimony alloy
separation  microporous separator
electrolyte 
 
sulphuric acid of 1,24 kg/l,
container  high stability by transparent halogene-free SAN, straight-walled containers
lid  halogene-free SAN in dark grey colour
pole bushing  100% gas- and electrolyte-tight, sliding-pole
kind of pole  M10 brass insertion
plugs  labyrinth plugs for arresting aerosol, optional ceramic plugs or ceramic funnel plugs acc. DIN 40 740
connector  flexible insulated cable connectors with insulated M10 pole bolts or insulated copper flat connectors
kind of protection  IP 25 regarding DIN 40050, touch protected according VBG 4

 

4. Charging
IU - characteristic   Imax without limitation 
U = 2,23 V/cell +- 1
boost charge  U = 2,40V/cell, time limited
charging time up to 90%  6h with 1,5*I10 initial current, 2.23 V/cell, 80% C3 discharged

 

5. Discharge characteristics
reference temperature 20°C
initial capacity 100%
depth of discharge  normally up to 80%
depth of discharges  more than 80% DOD or discharges beyond final discharge voltages
(dependent on discharge current) have to be avoided 

 

6. Maintenance
every 6 month  check battery voltage, pilot block voltage, temperature
every 12 month  take down battery voltage, block voltage, temperature,

 

7. Operational data
operational life  > 15 years at 20°C
> 7,5 years at 30°C
> 4 years at 40°C
water refilling interval  > 3 years at 20°C
IEC 896-1 cycles  1200
self-discharge  approx. 3% per month at 20°C
operational temperature  -20°C to 55°C
recommend 10°C to 30°C
ventilation requirement  f1=0,5 (low-antimony alloy)
according VDE 0510 part 2
measurements according  DIN 40 736 part 1
tests according  IEC 896-1,
applicable standards  VDE 0510, part 2
transport  no dangerous goods during road transport
Tell us your application. We support you in the selection of your battery.